ABB – ACS1000

Fuseless design for reliable, non-aging, maintenance-free circuit protection.

DTC control platform
for exceptionally high torque and speed performance.

IGCT power semiconductor
for highest reliability

Retrofit-ready
for existing motors and suitable for most medium voltage applications including pumps, fans, compressors, extruders, conveyors.

Output sine filter
for pure sinusoidal voltage and current output: standard motors, no motor derating, no voltage stress and no common mode voltages on the motor insulation.

Inverter type
Three-level Voltage Source Inverter (VSI) with fast-switching power semiconductors – Integrated Gate Commutated Thyristors (IGCTs), without parallel or series connected devices

Motors: Induction motors;
ACS 1000: 315 – 2000 kW air cooled
ACS 1000: 1800 – 5000 kW water cooled
ACS 1000i: 315 – 2000 kW air cooled
Auxiliary voltage
400 VAC ±10 %, 50 / 60 Hz
480 VAC ±10 %, 60 Hz
575 VAC ±10 %, 60 Hz, 3 phase